- NKK開關(guān)
- autonics奧托尼克斯
- 德國RAFI開關(guān)
-
APEM開關(guān)
- KACON凱昆
-
Idec和泉
-
Tapeswitch
-
Tokyo Sensor
-
Woonyoung
-
博思特
-
WEINVIEW威綸觸摸屏
-
快達Crydom繼電器
-
魏德米勒端子Weidmuller
-
歐姆龍
-
LUMEL
-
沙爾特寶Schaltbau
-
施耐德
-
SCHLEGEL?
-
EAO
-
Rittal威圖
-
HARTMANN
-
STMICROELECTRONI...
-
臺灣三巨SANJU Suntro...
-
東京傳感器
-
町洋
-
穆爾MURR
-
日本KEL連接器
-
臺灣明緯電源
- KOKUSAI國際電業(yè)
-
CH操縱工業(yè)手柄joystick...
- 德國Posital博思特編碼器F...
-
進口LED指示燈
-
Schaffner濾波器瑞士夏弗...
-
進口APEM開關(guān)switch
-
進口接線端子
- 壓電開關(guān)ROSSLARE金屬按鈕...
- Panasonic松下電器NAI...
-
Cosel科索開關(guān)電源模塊
-
SUNX松下神視Panasoni...
-
美國BELDEN百通電纜
-
工控設(shè)備
-
DKM電機
-
傳感器sensor
- 電子產(chǎn)品
-
SATO佐藤
-
韓國FASTECH
-
DELTA臺達
- -
- Nicomatic中國接插件電子...
-
Weidmuller魏德米勒
- encoder編碼器
-
KAVLICO傳感器kavlic...
-
進口Fuse熔斷器
-
變頻器inverter
- SIEMENS西門子
保護系統(tǒng)免受瞬態(tài)過電壓(雷擊)的影響Surge Protective Device
VR 1 + 2 型設(shè)計用于釋放高電流浪涌,而不會對設(shè)備造成任何破壞。
該浪涌保護裝置的特點是能夠承受 10/350 μs 波形的沖擊電流
模擬來自自然雷電流的直接沖擊。
1 型-2 型 SPD 放置在設(shè)備的入口點,位于主配電板中,可**保護設(shè)備。
T1 - T2
Imp : 25 kA
Din 每極 25kA 的沖擊電流(10/350 μs 波)滿足過壓浪涌保護的所有要求
其電子點火裝置在早期產(chǎn)生電弧會降低保護水平,可達 1.5kV
OVR T1+2 SPD 包含一個專用的電弧室,用于在放電后熄滅電弧,可以斷開短路。
低壓配電系統(tǒng)類型:TT、TN-S;
系統(tǒng)標(biāo)稱交流電壓 (Uo) : 230 / 400 V
保護極數(shù) : 2
避雷器等級 : I
產(chǎn)品主類型 : T1
標(biāo)準(zhǔn) : IEC 61643-1 / EN 61643-11
版本 : Fix
放電電流 : 標(biāo)稱 25 kA , Max. 60 kA , 總計 75 kA
脈沖電流 : I (imp, 10 / 350 μs) 25 kA
I (total, 10 / 350 μs) 50 kA
連續(xù)工作電壓 (Uc) : Max. (L-PE) 255 V , (L-L) - V
(L-N) 255 V , (N-PE) 255 V
電壓保護水平 ( Up) : (L-N) 2.5 kV ,(N-PE) 2 kV ,(L-PE) - kV
短路耐受 Icc : 50 kA
電流斷路容量 If (I fi) : 50 kA
暫態(tài)過壓測試值 (UT) : (L-N) 337 V , (N-PE) 1200 V
短路保護裝置:曲線 B 斷路器 ≤ 125 A
曲線 C 斷路器 ≤ 125 A
gL 型保險絲 ≤ 125 A
gG 型保險絲 ≤ 125 A
OVR T1 1N 25-255 Surge Protective Device 2CTB815101R1500
To protect the systems against the transient overvoltage (lightning)
OVR type 1 + 2 is designed to discharge high current surges without any destruction of the installation.
This surge protective device is chararcterized by its capacity to withstand impulse current with 10/350 μs wave form
which simulate direct impact coming from a natural lightning current.
Type 1-type 2 SPDs are placed at the entrance point of the installation, in the main distribution board for a global protection of this installation.
T1 - T2
Imp : 25 kA
· Din The impulse current of 25kA per pole (10/350 μs wave) satisfies all requirements for overvoltage surge protection
· The early creation of the electric arc by its electronic ignition device reduces the protection level Up to an otimum value of 1,5kV
· OVR T1+2 SPDs contain a dedicated arc chamber for extinguishing the electrical arc following the discharge, they can open short circuits.
Type of Low Voltage Distribution System : TT , TN-S ;
Nominal AC Voltage of the System (Uo) : 230 / 400 V
Number of Protected Poles : 2
Arrester Class : I
Product Main Type : T1
Standards : IEC 61643-1 / EN 61643-11
Version : Fix
Discharge Current : Nominal 25 kA , Maximum 60 kA ,Total 75 kA
Impulse Current : I (imp, 10 / 350 μs) 25 kA
I (total, 10 / 350 μs) 50 kA
Maximum Continuous Operating Voltage (Uc) : (L-PE) 255 V , (L-L) - V
(L-N) 255 V , (N-PE) 255 V
Voltage Protection Level ( Up) : (L-N) 2.5 kV ,(N-PE) 2 kV ,(L-PE) - kV
Short Circuit Withstand Icc : 50 kA
Follow Current Extinction Capacity If (I fi) : 50 kA
Temporary Overvoltage Test Value (UT) : (L-N) 337 V , (N-PE) 1200 V
Short-Circuit Protective Devices : Curve B Breakers ≤ 125 A
Curve C Breakers ≤ 125 A
gL Type Fuses ≤ 125 A
gG Type Fuses ≤ 125 A